Specifications
◆ Overview
AB-3S-12 series of circuit breakers is the company’s comprehensive domestic and foreign advanced technology, Bocaizhongzhijia long, using a new design concept, far from high-tech means, the latest development of a new generation of intelligent vacuum circuit breaker. The product can be used as 35kv substation main transformer 10kv side and 10kv outlet switch, can also be used as a distribution network on the column switch, and the company’s production is a combination of various control units can be easily achieved control, protection, Measurement, communication, is to achieve the automation and miniaturization of the preferred equipment.
◆ Model meaning
◆ conditions of use
1. Working environment temperature: not more than 40 ℃; daily average temperature of not more than 35; minimum ambient air temperature of -25 ;.
2. Air relative humidity: daily average of not more than 95%, the monthly average of not more than 90; water vapor pressure daily average of not more than 2.2kPa;
3. Monthly average is not more than 1.8 kPa;
4. Altitude: no more than 2000m;
5. The surroundings are not significantly contaminated by dust, smoke, corrosive and / or flammable gases, steam or salt fog;
6. The vibration or ground from outside the switchgear and control equipment is negligible;
7. In the secondary system, the amplitude of the induced electromagnetic interference does not exceed 1.6kv.
◆ Main technical parameters
Serial number | name | unit | data | |
1 | Rated voltage | KV | 12 | |
2 | Rated insulation level | 1min power frequency withstand voltage (RMS) | KV | 42 |
Lightning impulse withstand voltage (peak) | KV | 75 | ||
3 | Rated frequency | KV | 50 | |
4 | Rated current | A | 630 1250 | |
5 | Rated short circuit breaking current | KA | 20 | |
6 | Rated short-circuit closing current (peak) | KA | 50 | |
7 | Rated operating sequence | Points t1 (0.3s) – points t2 (3s) – points t2 (3s) – joint points – lock | ||
8 | Thermal stability current (4S) | KA | 20 | |
9 | Dynamic current (peak) | KA | 50 | |
10 | Rated short circuit current breaking times | Times | 30 | |
11 | CT ratio | 30-1250/1(5) | ||
12 | Working power supply voltage | V | -220(-110) | |
13 | Creepage distance | ≥ 31 | ||
14 | Number of machines | Times | 10000 | |
15 | weight | kg | 90+40 |
◆ main function
Protection: with or without time current quick current, timing overcurrent, reverse time overcurrent, directional overcurrent, over voltage, under voltage protection;
Control: can be in situ operation and remote control, can also be in accordance with the pre-set program action;
Automation: can automatically achieve the fault location of the line, fault isolation, restore power supply, parameter analysis;
Can be automatically required to achieve low-frequency load shedding, automatic switching capacitor, etc., and through GPRS or dedicated communication network to report fault information;
Communication: support TCP / IP protocol, support GPRS, provide CAN, RS232 / 485 communication port, support a variety of communication protocols (DNP3.0, IEC101, etc.)
Can record, store operation, operation and fault parameters, protection settings can be set on-site and remote programming;
Can monitor the mechanical parameters of the device, the arc chamber operation conditions;
Can be synchronized on the circuit breaker to effectively suppress the operation of over-voltage and inrush current, especially for the operation of the capacitor.